Commissioning – Lenze TML Flux Vector Drive 0.25kW-2.2kW User Manual

Page 17

Advertising
background image

Lenze 13466187 EDBTL03 v8

EN, DE, FR, IT, ES

15

Commissioning

Code

Possible Settings

IMPORTANT

No.

Name

Lenze Selection

C10

Minimum output

frequency

0.0

0.0 {Hz} 240 • Output frequency at 0% analog

setpoint

• C10 not active for fixed setpoints or

setpoint selection via c40

C11

Maximum output

frequency

50.0

7.5 {Hz} 240 • Output frequency at 100% analog

setpoint

• C11 is never exceeded

WARNING!

Consult motor/machine manufacturer before operating above rated frequency.

Overspeeding the motor/machine may cause damage to equipment and injury to

personnel!

C12

Acceleration time 1

5.0

0.0 {s} 999 • C12 = frequency change

0 Hz...C11

• C13 = frequency change

C11...0 Hz

• For S-ramp accel/decel, adjust c82

C13

Deceleration time 1

5.0

0.0 {s} 999

C14

Operating Mode

2

0 Linear characteristic with

Auto-Boost

• Linear characteristic: for standard

applications

• Square-law characteristic: for fans

and pumps with square-law load

characteristic

• Auto boost: load-dependent output

voltage for low-loss operation

1 Square-law characteristic with

Auto-Boost
2 Linear characteristic with constant

Vmin boost

3 Square-law characteristic with

constant Vmin boost

4 Vector speed control

• Vector speed control: for single-

motor applications requiring higher

starting torque and better speed

regulation

5 Vector torque control

• Vector torque control: for single-

motor applications requiring torque

control independent of speed

6 Enhanced linear characteristic

with Auto-Boost

• Enhanced: for single or multiple

motor applications that require better

performance than settings 0...3, but

cannot operate in vector mode

7 Enhanced linear characteristic with

constant Vmin boost

Note

• Settings 4...7 require Motor Calibration using c48

• Settings 4 and 5 require proper setting of C86...C91 prior to calibration

• Settings 6 and 7 require proper setting of C88...C90 prior to calibration

C15

V/f reference point

50.0

25.0 {Hz} 999

Set the rated motor frequency (nameplate)

for standard applications

smd006

C16

V

min

boost

(optimization of torque

behavior)

0.0 {%} 40.0
C16 not active in Vector mode (see C14)
Set after commissioning: The unloaded motor

should run at slip frequency (approx. 5 Hz),

increase C16 until motor current (C54) = 0.8 x

rated motor current

C17

Frequency threshold

(Q

min

)

0.0

0.0 {Hz} 240 See C08 selection 7, and CE3

selection 27