Rockwell Automation 48MS MultiSight Vision Sensor User Manual
Page 28
 
MultiSight™ User Manual
Start-up
28
10000000877(02)
Parameter
Description
Screen Shot
Logic
The Logic field allows the user to define how the detectors are 
linked together to determine the single OUT1 (pass/fail) output. A 
detector can be standalone (inspection of a single characteristic), 
logically linked (multiple inspections on a single part), or grouped 
(multiple inspections on different parts). (The concept is more 
thoroughly described in the above general description of the Select 
Detector window.) The state of the inspection output OUT1 
(passes/fails)/LED Q1 is determined by how the individual detector 
evaluation results are linked in the Logic field.
The evaluation of logically linked detectors is 
based on a single image. This means that 
certain detector parameters must be the 
same for all detectors that are logically 
linked together (see the chart below). The 
recommended procedure is to set the first 
detector in the group to the desired settings, 
then use the Copy command in the 
Commands window (on the left of the 
software screen, see page 24) to copy the 
configuration of that detector to the other 
detectors that will be logically linked.
The software will give the error message 
“group parameter check failed” when the 
sensor is put into run mode if detectors that 
are linked together have nonmatching 
parameters that should match.
IMPORTANT