Configuring the Adapter

3-5

20-COMM-L LonWorks Adapter User Manual

Publication 20COMM-UM008B-EN-P

Changes to these parameters take effect immediately. A reset is not
required.

Setting the Fault Configuration Parameters

When setting Parameter 6 - [Comm Flt Action] or 8 - [Idle Flt Action] to
‘Send Flt Cfg’, the values in the following parameters are sent to the drive
after an I/O communication fault and/or idle fault occurs. You must set
these parameters to values required by your application.

Changes to these parameters take effect immediately. A reset is not
required.

Setting an Idle Fault Action

Parameter 8 - [Idle Flt Action] lets you determine the action of the adapter
and connected drive when the node is taken offline.

Changing the Idle Action

Set the value of Parameter 8 - [Idle Flt Action] to an action that meets
your application requirements.

Changes to this parameter take effect immediately. A reset is not required.

Parameter

Description

11 - [Flt Cfg Logic] A 16-bit value sent to the drive for Logic Command.
12 - [Flt Cfg Ref]

A 32-bit value (0…4294967295) sent to the drive as a Reference or Datalink.

Important: If the drive uses a 16-bit Reference or 16-bit Datalinks, the most

significant word of the value must be set to zero (0) or a fault will occur.

13 - [Flt Cfg x1 In]

through

20 - [Flt Cfg x2 In]

Port 5 Device
20-COMM-L
Parameter #: 07

RcvHrtBeat Time

120.0

s

0 <> 3276.7

Default = 120.0 s

Port 5 Device
20-COMM-L
Parameter #: 08

Idle Flt Action

0

Fault

Value Action

Description

0

Fault

The drive is faulted and stopped.

(Default)

1

Stop

The drive is stopped, but not faulted.

2

Zero Data

The drive is sent ‘0’ values for data.

This does not command a stop.

3

Hold Last

The drive continues in its present state.

4

Send Flt Cfg The drive is sent the data that you set in

the fault configuration parameters

(

Parameters 11 - [Flt Cfg Logic]

through

20 - [Flt Cfg D2 In]).