Network configuration inputs (ncis), Network configuration inputs (ncis) -13, Network – Rockwell Automation 20-COMM-L LonWorks Adapter User Manual
Page 45: Configuration inputs (ncis)

Configuring the LonWorks Network
4-13
20-COMM-L LonWorks Adapter User Manual
Publication 20COMM-UM008B-EN-P
Network Configuration
Inputs (NCIs)
The values of the NCIs change when written to and keep their values after a
power cycle.
All NCIs, with a corresponding parameter in the drive, are read from the
drive after reset and when going from offline to online. When the parameter
is updated from the network, it is written to the drive.
NCI: nciSndHrtBt
Format: SNVT_time_sec
Explanation:
This network configuration input specifies the maximum send time for the
variable nvoDrvSpeed.
Valid Range: 0.0…6553.4 seconds
Default Value: 0.0 seconds (disabled)
NCI: nciRcvHrtBt
Format: SNVT_time_sec
Explanation:
This network configuration input specifies the maximum time that is
allowed to elapse between updates of the network variable input
nviDrvSpeedStpt. Setting nciRcvHrtBt to ‘0’ disables the Receive Heartbeat
function. If a timeout occurs, the adapter will implement a fault action in
Parameter 6 - [Comm Flt Action].
Valid Range: 0.0…6553.4 seconds
Default Value: 120.0 seconds
Send Heartbeat
Receive Heartbeat