Configuring the LonWorks Network

4-13

20-COMM-L LonWorks Adapter User Manual

Publication 20COMM-UM008B-EN-P

Network Configuration

Inputs (NCIs)

The values of the NCIs change when written to and keep their values after a
power cycle.

All NCIs, with a corresponding parameter in the drive, are read from the
drive after reset and when going from offline to online. When the parameter
is updated from the network, it is written to the drive.

NCI: nciSndHrtBt

Format: SNVT_time_sec

Explanation:

This network configuration input specifies the maximum send time for the
variable nvoDrvSpeed.

Valid Range: 0.0…6553.4 seconds

Default Value: 0.0 seconds (disabled)

NCI: nciRcvHrtBt

Format: SNVT_time_sec

Explanation:

This network configuration input specifies the maximum time that is
allowed to elapse between updates of the network variable input
nviDrvSpeedStpt. Setting nciRcvHrtBt to ‘0’ disables the Receive Heartbeat
function. If a timeout occurs, the adapter will implement a fault action in
Parameter 6 - [Comm Flt Action].

Valid Range: 0.0…6553.4 seconds

Default Value: 120.0 seconds

Send Heartbeat

Receive Heartbeat