Net a status indicator (service indicator), Viewing and clearing adapter diagnostic items – Rockwell Automation 20-COMM-L LonWorks Adapter User Manual

Page 55

Advertising
background image

Troubleshooting

5-3

20-COMM-L LonWorks Adapter User Manual

Publication 20COMM-UM008B-EN-P

NET A Status Indicator

(Service Indicator)

This red/green bicolor LED indicates the status of the network connection
as shown in the table below, and is controlled by the Neuron Chip.

Viewing and Clearing

Adapter Diagnostic Items

If you encounter unexpected communications problems, the adapter
diagnostic items can help you or Rockwell Automation personnel
troubleshoot the problem. Adapter diagnostic items can be viewed with any
of these drive configuration tools:

• LCD PowerFlex 7-Class HIM (Diagnostics/Device Items)

• Connected Components Workbench software, version 1.02 or later

• DriveExplorer software, version 2.01 or later

• DriveExecutive software, version 3.01 or later

Using the HIM to View and Clear Adapter Diagnostic Items

Status

Cause

Corrective Actions

Off

The node is configured.

No action required.

Flashing Red

WINK command received.

No action required.

Flashing Green

The node is not configured.

Configure the node.

Steady Green

The node has no application

program.

The Neuron Chip must be loaded with a new

application program.

Step

Example Screen

Viewing Diagnostic Items

1. Access parameters in the adapter.

See

Using the PowerFlex 7-Class HIM to Access Parameters on

page 3-2

.

2. Press the

or

key to scroll to

Diagnostics.

3. Press the

(Enter) key to display the Diagnostics menu in the

adapter.

4. Repeat steps 2 and 3 to enter the

Device Items option.

5. Press the

or

key to scroll through the items.

Clearing Diagnostic Items

1. Access parameters in the adapter.

See

Using the PowerFlex 7-Class HIM to Access Parameters on

page 3-2

.

2. Press the

or

key to scroll to

Parameter.

3. Press the

(Enter) key to display the list of parameters in the

adapter.

4. Repeat steps 2 and 3 to select

Parameter 22 - [Clear

Counters].

5. Set the value to ‘1’ (Clear) and press the

(Enter) key to

clear diagnostic items 26 and 27.

Main Menu:

Diagnostics

Parameter

Device Select

Device Item #

3

Reference

Main Menu:

Diagnostics

Parameter

Device Select

Parameter #22

Clear Counters

1

Clear

Advertising