B-2

Adapter Parameters

20-COMM-L LonWorks Adapter User Manual

Publication 20COMM-UM008B-EN-P

06

[Comm Flt Action]
Sets the action that the adapter and drive takes if the

adapter detects that network communication has been

disrupted (if

Parameter 7 - [RcvHrtBeat Time] times

out before nviDrvSpeedStpt is updated from the

network). This setting is effective only if I/O that

controls the drive is transmitted through the adapter.

Default:

0 = Fault

Values:

0 = Fault

1 = Stop

2 = Zero Data

3 = Hold Last

4 = Send Flt Cfg

Type:

Read/Write

Reset Required: No

07

[RcvHrtBeat Time]
Sets the time used as a Receive Heartbeat timer and

triggers the fault action in

Parameter 6 - [Comm Flt

Action].

Default:

120.0 seconds

Minimum:

0.0 seconds

Maximum:

3276.7 seconds

Type:

Read/Write

Reset Required: No

08

[Idle Flt Action]
Sets the action that the adapter and drive takes during

offline/disable occurrences.

Default:

0 = Fault

Values:

0 = Fault

1 = Stop

2 = Zero Data

3 = Hold Last

4 = Send Flt Cfg

Type:

Read/Write

Reset Required: No

Parameter
No. Name and Description

Details

!

ATTENTION: Risk of injury or equipment damage exists. Parameter 6 - [Comm

Flt Action] and Parameter 7 - [RcvHrtBeat Time] let you determine the action of

the adapter and connected drive if I/O communication is disrupted. By default, this

parameter faults the drive. You can set this parameter so that the drive continues

to run, however, take precautions to verify that the setting of this parameter does

not create a risk of injury or equipment damage. When commissioning the drive,

verify that your system responds correctly to various situations (for example, a

disconnected cable).

!

ATTENTION: Risk of injury or equipment damage exists. Parameter 7 -

[RcvHrtBeat Time] lets you determine how long it will take the adapter to detect a

loss of network communication. By default, this parameter sets the timeout to 120

seconds. You can set this parameter so that the duration is shorter, longer, or

disabled. When set to disabled (0 seconds), this also disables adapter

Parameter

6 - [Comm Flt Action]. Therefore, a communication fault action is ignored. Take

precautions to verify that the setting of this parameter does not create a risk of

injury or equipment damage. When commissioning the drive, verify that your

system responds correctly to various situations (for example, a disconnected

cable).

!

ATTENTION: Risk of injury or equipment damage exists. Parameter 8 - [Idle Flt

Action] lets you determine the action of the adapter and connected drive during

an offline/disable occurrence. By default, this parameter faults the drive. You can

set this parameter so that the drive continues to run, however, take precautions to

verify that the setting of this parameter does not create a risk of injury or

equipment damage. When commissioning the drive, verify that your system

responds correctly to various situations (for example, a disconnected cable).