Variable: nvoDrvSpeed

Format: SNVT_level_percent

Explanation:

This network variable output provides the speed of the drive as a percentage
of the nominal speed. This network variable output is also used as a
heartbeat to monitor the health of the LonWorks communication interface.

Default PowerFlex 70/700 Drive Parameter Mapping:

Parameter 1 - [Output Freq]

This can be mapped using the nviNV_config variable.

Variable: nvoDrvPwr

Format: SNVT_power_kilo

Explanation:

This network variable output provides the drive power in kilowatts.

Default PowerFlex 70/700 Drive Parameter Mapping:

Parameter 7 - [Output Power]

This can be mapped using the nviNV_config variable.

Variable: nvoDrvVolt

Format: SNVT_volt

Explanation:

This network variable output provides the drive voltage in volts.

Default PowerFlex 70/700 Drive Parameter Mapping:

Parameter 6 - [Output Voltage]

This can be mapped using the nviNV_config variable.

Drive Speed

Drive Power

Drive Voltage