Configuring the LonWorks Network

4-11

20-COMM-L LonWorks Adapter User Manual

Publication 20COMM-UM008B-EN-P

Variable: nvoDrvFreqAct

Format: SNVT_freq_hz

Explanation:

This network variable output provides the drive output frequency in Hz.
This value is always positive. It does not indicate the forward/reverse
direction of motor revolution.

Default PowerFlex 70/700 Drive Parameter Mapping:

Parameter 1 - [Output Freq]

This can be mapped using the nviNV_config variable or adapter Parameter
28 - [DrvFreqActParam]
.

Variable: nvoDrvRunHours

Format: SNVT_time_hour

Explanation:

This network variable output provides the drive total running time in whole
hours.

Default PowerFlex 70/700 Drive Parameter Mapping:

Parameter 10 - [Elapsed Run Time]

This can be mapped using the nviNV_config variable or adapter Parameter
27 - [DrvRunHoursParam]
.

Variable: nvoFB_config

Format: SNVT_count

Explanation:

This network variable output is used to verify that the configuration of the
adapter is correct. When changing the configuration with the nviNV_config
variable, nvoFB_config responds with the NV_index that was updated.

Output Frequency

Operation Hour Counter

Configuration Feedback