Adapter Parameters

B-3

20-COMM-L LonWorks Adapter User Manual

Publication 20COMM-UM008B-EN-P

09

[DPI I/O Cfg]
Sets the I/O that is transferred through the adapter.
NOTE: The Cmd/Ref bit must be set to control the

drive via the network. The respective Datalink bit(s)

must be set if the nvi/nvo Datalink variables are used.

Default:

xxx0 0001

Bit Values:

0 = I/O disabled

1 = I/O enabled

Type:

Read/Write

Reset Required: Yes

10

[DPI I/O Act]
Displays the I/O that the adapter is actively

transmitting. The value of this parameter is usually

equal to the value of

Parameter 9 - [DPI I/O Cfg].

Default:

xxx0 0001

Bit Values:

0 = I/O disabled

1 = I/O enabled

Type:

Read Only

11

[Flt Cfg Logic]
Sets the Logic Command data that is sent to the drive

if

Parameter 6 - [Comm Flt Action] is set to ‘4’ (Send

Flt Cfg) and communication is disrupted.
The bit definitions depend on the product to which the

adapter is connected. See

Appendix C

or the

documentation for the drive being used.

Default:

0000 0000 0000 0000

Minimum:

0000 0000 0000 0000

Maximum:

1111 1111 1111 1111

Type:

Read/Write

Reset Required: No

12

[Flt Cfg Ref]
Sets the Reference data that is sent to the drive if

Parameter 6 - [Comm Flt Action] is set to ‘4’ (Send

Flt Cfg) and communication is disrupted.
NOTE: This is a linear engineering unit value where ‘0’

equals 0 Hz. and 32,767 equals the Hz. value in the

PowerFlex 7-Class drive parameter 55 - [Maximum

Freq].

Default:

0

Minimum:

0

Maximum:

4294967295

Type:

Read/Write

Reset Required: No

Important: If the drive uses a 16-bit

Reference, the most significant word of

this value must be set to zero (0) or a

fault will occur.

13

14

15

16

17

18

19

20

[Flt Cfg A1 In]

[Flt Cfg A2 In]

[Flt Cfg B1 In]

[Flt Cfg B2 In]

[Flt Cfg C1 In]

[Flt Cfg C2 In]

[Flt Cfg D1 In]

[Flt Cfg D2 In]
Sets the data that is sent to the Datalink in the drive if

Parameter 6 - [Comm Flt Action] is set to ‘4’ (Send

Flt Cfg) and communication is disrupted.
NOTE: These are 32-bit values. If 16-bit Datalinks are

active, only the least significant word is used. If the

32-bit value is out of range for a 16-bit Datalink, a

configuration error forces a correction before I/O can

be enabled.

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Minimum:

0

Maximum:

4294967295

Type:

Read/Write

Reset Required: No

Important: If the drive uses 16-bit

Datalinks, the most significant word of

this value must be set to zero (0) or a

fault will occur.

Parameter
No. Name and Description

Details

Bit

Definition

No

t Us

ed

No

t Us

ed

No

t Us

ed

Da

ta

link

D

Da

ta

link

C

Da

ta

link

B

Da

ta

link

A

Cmd/Ref

Default

x

x

x

0

0

0

0

1

Bit

7

6

5

4

3

2

1

0

Bit

Definition

No

t Us

ed

No

t Us

ed

No

t Us

ed

Da

ta

link

D

Da

ta

link

C

Da

ta

link

B

Da

ta

link

A

Cmd/Ref

Default

x

x

x

0

0

0

0

1

Bit

7

6

5

4

3

2

1

0

Advertising