Configuring the LonWorks Network

4-9

20-COMM-L LonWorks Adapter User Manual

Publication 20COMM-UM008B-EN-P

Network Variable Outputs

(NVOs)

This section describes the network variable outputs. No output values are
sent over the network, unless they have changed (except nvoDrvSpeed,
which is sent for the heartbeat functionality, and nvoObjStatus, if update
status is requested).

Variable: nvoObjStatus

Format: SNVT_obj_status

Explanation:

This network variable output reports node object status and is updated every
time its status changes (see

Node Object Request on page 4-5

).

Valid Range:

Variable: nvoDrvStatus

Format: SNVT_state

Explanation:

This network variable output provides the status of the drive by way of the
Logic Status word (see

Appendix C

).

Variable: nvoDrvCurnt

Format: SNVT_amp

Explanation:

This network variable output provides the drive output current in amps.

Default PowerFlex 70/700 Drive Parameter Mapping:

Parameter 3 - [Output Current]

This can be mapped using the nviNV_config variable.

Node Object Status

Invalid_ID

The node has been asked for an invalid object ID.

Invalid_IDrequest

The node has been asked for an unsupported request.

Report_mask

Report supported fields.

Comm_failure

No contact with DPI.

In_alarm

The drive is faulted.

Manual_control

The drive is not controlled from the LonWorks peripheral.

Drive Status

Drive Current