Appendix b, Adapter parameters, About parameter numbers – Rockwell Automation 20-COMM-L LonWorks Adapter User Manual

Page 61: Parameter list, Badapter parameters, Appendix

Advertising
background image

20-COMM-L LonWorks Adapter User Manual

Publication 20COMM-UM008B-EN-P

Appendix

B

Adapter Parameters

Appendix B provides information about the adapter parameters.

About Parameter Numbers

The parameters in the adapter are numbered consecutively.

Parameter List

Topic

Page

About Parameter Numbers

B-1

Parameter List

B-1

Configuration Tool

Numbering Scheme

• HIM

• DriveExplorer

• DriveExecutive

The adapter parameters begin with parameter 01. For example,

Parameter 01 - [DPI Port] is parameter 01 as indicated by this manual.

Parameter
No. Name and Description

Details

01

[DPI Port]
Displays the port to which the adapter is connected.

This usually is port 5.

Minimum:

0

Maximum:

7

Type:

Read Only

02

[DPI Data Rate]
Displays the data rate used by the drive. This data rate

is set in the drive and the adapter detects it.

Values:

0 = 125 kbps

1 = 500 kbps

Type:

Read Only

03

[Ref/Fdbk Size]
Displays the size of the Reference/Feedback. The

drive determines the size of the Reference/Feedback.

Values:

0 = 16-bit

1 = 32-bit

Type:

Read Only

04

[Datalink Size]
Displays the size of each Datalink word. The drive

determines the size of Datalinks.

Values:

0 = 16-bit

1 = 32-bit

Type:

Read Only

05

[Reset Module]
No action if set to ‘0’ (Ready). Resets the adapter if set

to ‘1’ (Reset Module). Restores the adapter to its

factory default settings if set to ‘2’ (Set Defaults). This

parameter is a command. It resets to ‘0’ (Ready) after

the command has been performed.

Default:

0 = Ready

Values:

0 = Ready

1 = Reset Module

2 = Set Defaults

Type:

Read/Write

Reset Required: No

!

ATTENTION: Risk of injury or equipment damage exists. If the adapter is

transmitting I/O that controls the drive, the drive can fault when you reset the

adapter. Determine how your drive will respond before resetting a connected

adapter.

Advertising