Rockwell Automation 20-COMM-L LonWorks Adapter User Manual

Page 64

Advertising
background image

B-4

Adapter Parameters

20-COMM-L LonWorks Adapter User Manual

Publication 20COMM-UM008B-EN-P

21

[Send Service Pin]
Broadcasts a LON Service Pin Message from the

Neuron Chip. This provides the Neuron ID.
An alternate method for providing the Neuron ID is to

enter the ID number manually. The Neuron ID can be

viewed using Diagnostic Item # 30 (see

page 5-4

).

Default:

0 = Ready

Values:

0 = Ready

1 = Send

Type:

Read/Write

Reset Required: No

22

[Clear Counters]
Clears the network diagnostic counters (Diagnostic

Items # 26 and 27; see

page 5-4

).

Default:

0 = Ready

Values:

0 = Ready

1 = Clear

Type:

Read/Write

Reset Required: No

23

[DrvSpeedParam]
Sets the PowerFlex 7-Class drive parameter number to

be used with nvoDrvSpeed (see

page 4-10

).

Setting this parameter value to ‘0’ disables the adapter

from retrieving the corresponding parameter value

from the drive.

Default:

1

Values:

PowerFlex 7-Class

drive parameter

numbers

Type:

Read/Write

Reset Required: Yes

24

[DrvCurntParam]
Sets the PowerFlex 7-Class drive parameter number to

be used with nvoDrvCurnt (see

page 4-9

).

Setting this parameter value to ‘0’ disables the adapter

from retrieving the corresponding parameter value

from the drive.

Default:

3

Values:

PowerFlex 7-Class

drive parameter

numbers

Type:

Read/Write

Reset Required: Yes

25

[DrvPwrParam]
Sets the PowerFlex 7-Class drive parameter number to

be used with nvoDrvPwr (see

page 4-10

).

Setting this parameter value to ‘0’ disables the adapter

from retrieving the corresponding parameter value

from the drive.

Default:

7

Values:

PowerFlex 7-Class

drive parameter

numbers

Type:

Read/Write

Reset Required: Yes

26

[DrvVoltParam]
Sets the PowerFlex 7-Class drive parameter number to

be used with nvoDrvVolt (see

page 4-10

).

Setting this parameter value to ‘0’ disables the adapter

from retrieving the corresponding parameter value

from the drive.

Default:

6

Values:

PowerFlex 7-Class

drive parameter

numbers

Type:

Read/Write

Reset Required: Yes

27

[DrvRunHoursParam]
Sets the PowerFlex 7-Class drive parameter number to

be used with nvoDrvRunHours (see

page 4-11

).

Setting this parameter value to ‘0’ disables the adapter

from retrieving the corresponding parameter value

from the drive.

Default:

10

Values:

PowerFlex 7-Class

drive parameter

numbers

Type:

Read/Write

Reset Required: Yes

28

[DrvFrqActParam]
Sets the PowerFlex 7-Class drive parameter number to

be used with nvoDrvFreqAct (see

page 4-11

).

Setting this parameter value to ‘0’ disables the adapter

from retrieving the corresponding parameter value

from the drive.

Default:

1

Values:

PowerFlex 7-Class

drive parameter

numbers

Type:

Read/Write

Reset Required: Yes

29

[NmlFreqParam]
Sets the PowerFlex 7-Class drive parameter number to

be used with nciNmlFreq (see

page 4-11

).

Default:

43

Values:

PowerFlex 7-Class

drive parameter

numbers

Type:

Read/Write

Reset Required: Yes

Parameter
No. Name and Description

Details