Setting the fault configuration parameters – Rockwell Automation 20-750-PNET Profinet Single Port Option Module User Manual

Page 34

Advertising
background image

34

Rockwell Automation Publication 750COM-UM006A-EN-P - January 2013

Chapter 3 Configuring the Option Module

Setting the Fault Configuration Parameters

When setting

Host Parameters 33 - [Comm Flt Action] and 34 - [Idle Flt

Action] to ‘Send Flt Cfg’, the values in the following parameters are sent to the
drive after a communication fault and/or idle fault occurs. You must set these
parameters to values required by your application.

Changes to these parameters take effect immediately. A reset is not required.

Option Module Host Parameter

Description

Parameter 37 - [Flt Cfg Logic]

A 32-bit value sent to the drive for Logic Command.

Parameter 38 - [Flt Cfg Ref]

A 32-bit REAL (floating point) value sent to the drive for
Reference.

Parameter 39 - [Flt Cfg DL 01]

through

Parameter 54 - [Flt Cfg DL 16]

A 32-bit integer value sent to the drive for a Datalink. If the
destination of the Datalink is a REAL (floating point)
parameter, you must convert the desired value to the binary
representation of the REAL value. (An internet search of ‘hex
to float’ provides a link to a tool to do this conversion.)