Setting the Fault Configuration Parameters
When setting
Host Parameters 33 - [Comm Flt Action] and 34 - [Idle Flt
Action] to ‘Send Flt Cfg’, the values in the following parameters are sent to the
drive after a communication fault and/or idle fault occurs. You must set these
parameters to values required by your application.
Changes to these parameters take effect immediately. A reset is not required.
Option Module Host Parameter
Description
Parameter 37 - [Flt Cfg Logic]
A 32-bit value sent to the drive for Logic Command.
Parameter 38 - [Flt Cfg Ref]
A 32-bit REAL (floating point) value sent to the drive for
Reference.
Parameter 39 - [Flt Cfg DL 01]
through
Parameter 54 - [Flt Cfg DL 16]
A 32-bit integer value sent to the drive for a Datalink. If the
destination of the Datalink is a REAL (floating point)
parameter, you must convert the desired value to the binary
representation of the REAL value. (An internet search of ‘hex
to float’ provides a link to a tool to do this conversion.)