Rockwell Automation 20-750-PNET Profinet Single Port Option Module User Manual

Page 52

Advertising
background image

52

Rockwell Automation Publication 750COM-UM006A-EN-P - January 2013

Chapter 6 Acyclic Messaging

Write Example for Drive Parameter 535 - [Accel Time 1]

To perform a Write operation, manually enter the values as shown below in the
Read/Write Record window:

• Index = Parameter number = 535 = 0x217
• Write Length = Length in bytes of the value of the parameter (32-bit

value) = 4

1.

Manually enter the value ‘41 20 00 00’ in the Write Data (hex) section
(this value is equal to 10.00 seconds).

2.

Click Write Record.

The Write response is displayed in the Write Data (hex) section.

The value of drive Parameter 535 - [Accel Time 1] has been changed per
the entered value in the Write Data (Hex section).

Advertising