Chapter 3 Configuring the Option Module

9.

Reset the option module using

Device Parameter 05 - [Reset Module] or

by cycling power to the drive so that the restored parameters take effect.

Viewing the Option Module
Status Using Parameters

The following parameters provide information about the status of the option
module. You can view these parameters at any time.

Updating the Option
Module Firmware

The option module firmware can be updated over the network through a direct
connection from a computer to only the 20-750-PNET option module. You can
use the Allen-Bradley ControlFLASH software tool, the built-in update
capability of DriveExplorer Lite or Full software, or the built-in update capability
of DriveExecutive software.

To obtain a firmware update for this option module, go to

http://www.ab.com/

support/abdrives/webupdate

. This website contains all firmware update files and

associated Release Notes that describe the following items:

• Firmware update enhancements and anomalies
• How to determine the existing firmware revision
• How to update the firmware using DriveExplorer, DriveExecutive, or

ControlFLASH software

Option Module
Device
Parameter

Description

02 - [DLs From Net Act]

The number of controller-to-drive Datalinks that are included in the
network I/O connection (controller outputs).

03 - [DLs To Net Act]

The number of drive-to-controller Datalinks that are included in the
network I/O connection (controller inputs).

04 - [Net Addr Src]

Displays the source from which the option module network address is
taken. It is either the values of configured option module parameters
or from DCP-DHCP.

IMPORTANT

To update the option module, the IP Address Selection Jumper must be
connected across pins 2 and 3. This can be easily verified by viewing the
value of read-only Device Parameter 04 - [Net Addr Src], which must
be ‘1’ (Config). If the value is ‘0’ (DCP-DHCP), you must change the IP
Address Selection Jumper from being across pins 1 and 2 to being across
pins 2 and 3.