Rockwell Automation Publication 750-IN027C-EN-P - November 2013
PowerFlex 755 Transition Section and Splicing Kit for Floor-mount Drives and CENTERLINE 2100 Motor Control Centers
Step 4 (Right): Join PE Bus Bar and Grounding Bracket
1.
Align the protective earth (PE) conductor splicing hardware with the
transition section grounding bracket.
2.
Insert and tighten the 1/4-20 x 1 in. screws.
IMPORTANT
Do not grease or lubricate hardware.
1/4-20 x 1 in.
7.3 N•m (65 lb•in)
10 mm