Step 7: join horizontal bus and splicing bars – Rockwell Automation 21G PowerFlex 755 Transition Section and Splicing Kit User Manual

Page 20

Advertising
background image

20

Rockwell Automation Publication 750-IN027C-EN-P - November 2013

PowerFlex 755 Transition Section and Splicing Kit for Floor-mount Drives and CENTERLINE 2100 Motor Control Centers

Step 7: Join Horizontal Bus and Splicing Bars

Splicing kits will contain either two or four sets of hardware per splice bar,
depending on the current rating of the horizontal bus. Assemble hardware as
depicted in

Figure 2

and uniformly tighten splice kit hardware to the final torque

listed in

Table 1

.

Figure 2 - Splicing Hardware Configuration Detail

See

Table 3

for main horizontal bus-bar splicing bar dimensions.

IMPORTANT

Note for NO-OX-ID: If you’re using corrosion inhibitor on bus bars, do not get
any on the bus splicing hardware. It will prevent the hardware from being
properly torqued. Damage may occur.

Main Horizontal Bus -bar

Main Horizontal
Bus-bar Splicing Bars

Flat Washers

One-Piece Nut and Conical Spring Washer

Bus Clamps

Front

Advertising