Rockwell Automation 21G PowerFlex 755 Transition Section and Splicing Kit User Manual

Page 8

Advertising
background image

8

Rockwell Automation Publication 750-IN027C-EN-P - November 2013

PowerFlex 755 Transition Section and Splicing Kit for Floor-mount Drives and CENTERLINE 2100 Motor Control Centers

3.

Bring the transition section and drive cabinet together.

4.

Pass the M6 x 16 mm hex-head thread-forming screws from inside the
transition section through the joining holes and engage the screws with the

holes in the drive cabinet.

5.

Make sure cabinets are level and pushed together tightly.

6.

Tighten the screws in a uniform pattern.

IMPORTANT

Do not use hardware to draw cabinets together.

M6

6.2 N•m (55 lb•in)

10 mm

Advertising