Local and Serial Port Parameters
Firmware Version 1.01-3.01

Chapter 3

3-25

Parameter 36 Ċ MOPC

Freq

P

R

P

R

Enter

% of Rated Output Current
50
115
115

Read and Write
Units
Minimum Value
Maximum Value
Factory Setting

Important: Overload Current (Parameter 38) limits the drive output
current independent of the setting of Parameter 36. The overload range
available from the drive will be limited by the lower of the two settings. If
the setting of Parameter 36 is greater than the setting of Parameter 38, an
overload condition could occur before MOPC is activated.

The value of this parameter adjusts the Momentary Overload Protection
Circuit setting of the drive in units of % of rated output current. When the
drive output current attempts to exceed this value, the drive will respond by
reducing frequency and voltage to limit drive output current to this value.
Once output current is reduced below this value, the drive will ramp back
to command frequency.