Serial Port Parameters
Firmware Version 1.01-3.01

Chapter 4

4-9

Parameter 60 Ċ Drive Alarm

Read Only

Units

Byte

Min Value

0

Max Value

255

This parameter is an eight-bit word that shows the status of the six
possible drive alarm conditions.

BIT 0 — Drive Output Current — 0 = output current below 115%

1 = output current above 115%

BIT 1 — MOPC Limit

0 = output current is below MOPC

limit set by Parameter 36

1 = output current is above MOPC

limit set by Parameter 36

BIT 2 — High Bus Voltage

0 = bus voltage below 110% of

nominal input voltage

1 = bus voltage above 110% of

nominal input voltage —
Frequency Hold is active if
Parameter 11 is set to 1

BIT 3 — Low Bus Voltage

0 = bus voltage above 85% of

nominal input voltage

1 = bus voltage below 85% of

nominal input voltage

BIT 4 — not used

BIT 5 — precharge

0 = precharge complete

1 = precharge not complete

BIT 6 — Auto Restart Alarm

0 = Auto Restart function inactive

1 = Auto Restart function active

(Refer to Parameter 85)

BIT 7 — not used