Rockwell Automation 1336VT AC DRIVE 5-300AMP (2-160KW) PROGRAMMING MANUAL User Manual
Page 59

Serial Port Parameters
Firmware Version 1.01-3.01
Chapter 4
4-9
Parameter 60 Ċ Drive Alarm
Read Only
Units
Byte
Min Value
0
Max Value
255
This parameter is an eight-bit word that shows the status of the six
possible drive alarm conditions.
BIT 0 — Drive Output Current — 0 = output current below 115%
1 = output current above 115%
BIT 1 — MOPC Limit
— 0 = output current is below MOPC
limit set by Parameter 36
1 = output current is above MOPC
limit set by Parameter 36
BIT 2 — High Bus Voltage
— 0 = bus voltage below 110% of
nominal input voltage
1 = bus voltage above 110% of
nominal input voltage —
Frequency Hold is active if
Parameter 11 is set to 1
BIT 3 — Low Bus Voltage
— 0 = bus voltage above 85% of
nominal input voltage
1 = bus voltage below 85% of
nominal input voltage
BIT 4 — not used
BIT 5 — precharge
— 0 = precharge complete
1 = precharge not complete
BIT 6 — Auto Restart Alarm
— 0 = Auto Restart function inactive
1 = Auto Restart function active
(Refer to Parameter 85)
BIT 7 — not used