Local and Serial Port Parameters
Firmware Version 1.01-3.01

Chapter 3

3-35

Parameters 48Ć50

Important: Parameters 48-50 may be used to program a custom
volts-per-hertz curve for the 1336VT for special motor applications.

0

300V AC

100V AC

200V AC

400V AC

500V AC

10 Hz

30 Hz

50 Hz

60 Hz

80 Hz

100 Hz

20 Hz

40 Hz

70 Hz

90 Hz

1

Boost

2

4

1 Parameter 48 Start Boost = 100 Volts

2 Parameter 49 Break Frequency = 20 Hertz
Parameter 50 Break Volts = 200 Volts

3 Parameter 17 Base Frequency = 60 Hertz
Parameter 18 Base Volts = 460 Volts

4 Parameter 19 Maximum Frequency = 100 Hertz
Parameter 20 Maximum Volts = 460 Volts

3

Parameter 9 = 11 -- Custom VoltsĆperĆHertz

Parameter 48 -- Start Boost

Freq

P

R

P

R

Enter

Volts
0
115
0

Read and Write
Units
Minimum Value
Maximum Value
Factory Setting

Important: If Run Boost (Parameter 83) is greater than Start Boost, the
drive will fault and display F34 –– Boost Error.

The parameter sets the drive boost voltage if Parameter 9 is set to 11. This
parameter along with Parameters 49 and 50 are used to construct a custom
volts-per-hertz curve. If Parameter 83 (Run Boost) is required, this
parameter must be set to a value greater than Run Boost and Parameter 9
must be set to 12.