Serial Port Parameters
Firmware Version 1.01-3.01

Chapter 4

4-7

Parameter 58 Ċ Drive Command

Read Only

Units

Byte

Min Value

0

Max Value

255

This parameter represents the status of various inputs that control the drive.
It is an eight-bit word but only five bits contain actual status information.

BIT 0 — Direction

0 = forward

1 = reverse

BIT 1 — Enable

0 = drive (not) enabled

1 = drive enabled

BIT 2 — Run

0 = stop (Run command not present)

1 = run (Run command present)

BIT 3 — Accel Time

0 = use Accel Time 1, Parameter 7

1 = use Accel Time 2, Parameter 30

BIT 4 — Decel Time

0 = use Decel Time 1, Parameter 8

1 = use Decel Time 2, Parameter 31

BIT 5 — not defined

BIT 6 — not defined

BIT 7 — not defined