Serial Port Parameters
Firmware Version 1.01-3.01
Chapter 4
4-6
Parameter 57 Ċ Serial Mask
BIT 4 — Jog
— 0 = drive will not accept Jog
(cont.)
command bit
1 = Jog at Jog Frequency, Parameter
24, may be selected.
BIT 5 — Direction
— 0 = drive will not accept Direction
command bit.
1 = direction change allowed.
BIT 6 — Stop
— 0 = data will not stop drive.
1 = data will stop drive.
BIT 7 — Start
— 0 = data will not start drive.
1 = data will start drive.