Chapter – Rockwell Automation 1336VT AC DRIVE 5-300AMP (2-160KW) PROGRAMMING MANUAL User Manual
Page 82

11
Chapter
11-1
Local and Serial Port Parameter Settings
Firmware Version 2.01 and 3.01
Table 11 -- Parameter List for Parameters 70 to 89
Parameters 70 to 89
are local and serial port parameters that may only be
accessed with Firmware Version 2.01 and 3.01.
Local
Programming
Serial
Panel
Port
Parameter Parameter
Min/Max
Min/Max
Factory
Number
Text
Units
Values
Values
Setting
70
BASE DRIVER BOARD VERSION
Code
---
---
---
71
CONTROL BOARD VERSION
Code
---
---
---
72
ACTIVATE PARAMETERS 73Ć76
Off/On
0/1
0/1
0
73
PRESET FREQUENCY 4
Hertz
.0/250
0.00/250.00
.0
74
PRESET FREQUENCY 5
Hertz
.0/250
0.00/250.00
.0
75
PRESET FREQUENCY 6
Hertz
.0/250
0.00/250.00
.0
76
PRESET FREQUENCY 7
Hertz
.0/250
0.00/250.00
.0
77
ABOVE FREQUENCY CONTACT Hertz
0/250
0/250
0
78
TRAVERSE PERIOD
Seconds
0/30
0.00/30.00
0
79
MAXIMUM TRAVERSE
Hertz
.0/100
0.00/100.00
.0
80
INERTIA COMPENSATION
Hertz
.0/20.0
0.00/20.00
.0
81
SOFT START/STOP ENABLE
Off/On
---
---
---
82
AMP LIMIT FAULT ENABLE
Off/On
0/1
0/1
0
83
RUN BOOST
Volts
0/115
0/115
0
84
ANALOG INVERSE
Off/On
0/1
0/1
0
85
RESTART TRIES
Code
0/9
0/9
0
86
FAULT BUFFER 0
Code
0/37
0/37
87
FAULT BUFFER 1
Code
0/37
0/37
---
88
FAULT BUFFER 2
Code
0/37
0/37
---
89
FAULT BUFFER 3
Code
0/37
0/37
---