This group of parameters allows configuring, viewing and clearing drive faults.
[Fault Buffer 0]
[Fault Buffer 1]
[Fault Buffer 2]
[Fault Buffer 3]
These parameters store the last (4) faults that occur.
Parameter Number
86-89
Parameter Type
Read and Write
Factory Default
None
Units
Display Drive
“0” 0
Last Fault
“1” 1
Fault from Buffer 0
“2” 2
Fault from Buffer 1
“3” 3
Fault from Buffer 2
[Clear Fault]
Selecting “Clear Fault” and pressing Enter will clear any
faults and return the drive to ready status.
Parameter Number
51
Parameter Type
Read and Write
Factory Default
“Ready”
Units
Display Drive
“Ready” 0
“Clear Fault” 1
[Cur Lim Trip En]
This setting determines the drive response when the hard-
ware current limit is exceeded. The current limit is
approximately 180% of [Rated VT Amps] for B Frame
drives & up, and approximately 250% of [Rated VT Amps]
for A Frame drives.
Parameter Number
82
Parameter Type
Read and Write
Factory Default
“Disabled”
Units
Display Drive
“Disabled” 0
No Fault Generated - C.L. Activated
“Enabled” 1
Diag C Lim Flt Generated
[Shear Pin Fault]
Enabling this parameter allows the drive to generate a
Shear Pin Fault (F63) if the output amps exceed the pro-
grammed software current limit value in [Current Limit].
When set to “Not Accel” the fault will not be enabled until
the drive is “at speed.”
Parameter Number
226
Parameter Type
Read and Write
Factory Default
“Disabled”
Units
Display Drive
“Disabled” 0
No Fault Generated
“Enabled” 1
Fault Generated, All Conditions
“Not Accel” 2
No Fault Generated during Accel
[Motor OL Fault]
This parameter enables or disables the motor overload
protection feature of the drive.
Parameter Number
201
Parameter Type
Read and Write
Factory Default
“Enabled”
Units
Display Drive
“Disabled” 0
No Fault Generated
“Enabled” 1
Fault Generated
[Motor Therm Flt]
This parameter enables or disables the motor thermal pro-
tection feature of the drive. The LA6 option board must be
installed.
Parameter Number
268
Parameter Type
Read and Write
Factory Default
“Enabled”
Units
Display Drive
“Disabled” 0
No Fault Generated
“Enabled” 1
Fault Generated
[Line Loss Fault]
This parameter enables or disables a Power Loss Fault
(F03), 0.5 seconds after a Line Loss in Progress alarm.
Parameter Number
40
Parameter Type
Read and Write
Factory Default
“Disabled”
Units
Display Drive
“Disabled” 0
No Fault Generated
“Enabled” 1
Power Loss Fault Generated