Kp process, Pi neg limit, Pi pos limit – Rockwell Automation 1336F PLUS II User Manual - Firmware 1.xxx-6.xxx User Manual
Page 138: Pi preload, Process pi

6–56
Programming
[KP Process]
This parameter sets the proportional gain of the process
PI loop.
Parameter Number
222
Parameter Type
Read/Write
Display Units / Drive Units
NA / NA
Factory Default
256
Minimum Value
0
Maximum Value
1024
[PI Neg Limit]
This parameter sets the lower (negative) limit of the PI
output.
Parameter Number
223
Parameter Type
Read/Write
Display Units / Drive Units
0.01 Hertz / 32767 = Maximum Freq Forward
Factory Default
–8.33% of [Maximum Freq]
Minimum Value
–400.00 Hz
Maximum Value
400.00 Hz
[PI Pos Limit]
This parameter sets the upper (positive) limit of the PI
output.
Parameter Number
224
Parameter Type
Read/Write
Display Units / Drive Units
0.01 Hertz / 32767 = Maximum Freq Forward
Factory Default
+8.33% of [Maximum Freq]
Minimum Value
–400.00 Hz
Maximum Value
400.00 Hz
[PI Preload]
Sets the value used to preload the PI integrator when “Set
Output” or “Preload Int” bits equal “1” in [PI Config].
Parameter Number
225
Parameter Type
Read/Write
Display Units / Drive Units
0.01 Hertz /
±32767 = Maximum Freq
Factory Default
0.00 Hz
Minimum Value
– 8.33% of [Maximum Freq]
Maximum Value
+8.33% of [Maximum Freq]