Troubleshooting
Hertz Sel Fault
30
A frequency select parameter has
been programmed with an out of
range value.
Reprogram [Freq Select 1] and/or
[Freq Select 2] with a correct value. If
problem persists, replace Main Con-
trol Board or complete drive.
HIM -> Drive
Refer to
.
Ill Prog Input
62
[Fault Data] = 98 – “3 Wire” is
selected as the [Input Mode] and
one or more digital inputs are pro-
grammed to “Run Reverse” (2
wire action).
Reprogram the digital inputs or select
“2 Wire” as the [Input Mode].
Input Phase Flt
49
The DC bus ripple has exceeded
the value in [Phase Loss Level].
1. If the drive is operated on single-
phase, the load derating level has
been exceeded.
2. Check incoming power for a miss-
ing phase/blown fuse.
Load Loss Flt
20
[Load Loss Detect] is set to
“Enabled” and the drive output
torque current was below [Load
Loss Level] for a time period
greater than [Load Loss time].
1. Verify connections between motor
and load.
2. Verify level and time requirements
or disable [Load Loss Detect].
Loop Overrn Flt
23
An overrun of the 2.5ms control
loop has occurred.
Check all connections to the Main
Control Board. Replace the board or
complete drive as needed.
Max Retries Fault
33
Drive unsuccessfully attempted to
reset a fault and resume running
for the programmed number of
[Reset/Run Tries].
Check fault buffer for fault code
requiring reset. Correct the cause of
the fault and manually clear by press-
ing the local Stop key or cycling the
TB3 Stop input.
Motor Mode Flt
24
A fault has been detected origi-
nating from the Control Board.
Check all connections to the Control
Board. Replace the board or com-
plete drive as required.
Motor Stall Fault
06
Current remained over [Current
Limit] setting (parameter 36) for
more than 4 seconds.
If the motor is drawing excessive cur-
rent (over [Current Limit] setting), the
motor load is excessive and will not
allow the drive to accelerate to set
speed. A longer accel time or a
reduced load may be required.
Motor Thermistor
15
An analog option board with ther-
mistor input is installed and the
value at the terminals is less than
60 ohms or greater than 3300
ohms.
1. Verify that thermistor is connected.
2. Motor is overheated. Reduce load.
3. Thermistor is not present. Remove
option board.
Mult Prog Input
61
A single source input function
such as Reverse/Forward
(open=1
st
function, closed=2
nd
function) has been programmed
to more than one input or more
than one “Run Reverse” input.
Reprogram one or more of the inputs
to a different value.
Neg Slope Fault
35
Drive software detected a portion
of the volts/hertz curve with a
negative slope.
Check drive programming.
1. [Base Voltage] parameter must be
greater than [Start Boost].
2. If the [DC Boost Select] parameter
is set to “Full Custom,” [Base Volt-
age] must be greater than [Break
Voltage] and [Break Voltage] must
be greater than [Start Boost].
Name & Fault #
Description
Action