Troubleshooting
Table 7.E
(continued)
Alarm Conditions
Alarm
Bit
Alarm Name
Description
[Drive
Alarm 2]
0
Motor Therm
The value at the thermistor terminals has been exceeded. This bit will be active only when [Motor
Therm Flt] is enabled and an analog option board with thermistor input is installed.
1
Load Loss
[Load Loss Detect] is set to “Enabled” and the drive output torque current was below [Load Loss
Level] for a time period greater than [Load Loss time].
2
Encoder Loss
Error has occurred in the encoder signals at TB3, terminals 31-36.
3
Enc Cnt Set
[Encoder Counts] has reached the endpoint of
±
32767
.
4
Enc Cnt Max
The value of [Encoder Counts] has exceeded [Max Enc Counts].
5
Voltage Check
Voltage at drive output terminals is equal to, or greater than 10% of drive rated volts (i.e. 46V for 460V
drive) when Start command is issued and flying start is disabled. Drive will not start until terminal
voltage falls below 10% of drive rating or flying start is enabled.