Alarm mask 1, Alarm mask 2, Masks – Rockwell Automation 1336F PLUS II User Manual - Firmware 1.xxx-6.xxx User Manual
Page 127

Programming
6–45
[Alarm Mask 1]
Controls which alarm conditions will ac-
tivate the alarm contact (refer to Chapter
2 - TB2) and set the alarm bit (bit 6) in
[Drive Status 1].
A Status description (bit ENUM) is dis-
played on line 1 (except Series A HIMs
below version 3.0).
Parameter Number
206
Parameter Type
Read and Write
Factory Default
1111111111111111
[Alarm Mask 2]
Controls which alarm conditions will ac-
tivate the alarm contact (refer to Chapter
2 - TB2) and set the alarm bit (bit 6) in
[Drive Status 1].
Setting the bit to “1” allows the alarm to
occur. Setting the bit to “0” causes the
drive to ignore that alarm.
A Status description (bit ENUM) is dis-
played on line 1 (except Series A HIMs
below version 3.0).
Parameter Number
271
Parameter Type
Read and Write
Factory Default
1111111111111111
Bus Charging
Regenerating Current Limit
Regenerating Voltage Limit
Line Loss In Progress
Motor Stalled
Ground Warning
Bit 15
Bit 13 Bit 12 Bit 11 Bit 10 Bit 9 Bit 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Mtr Overload
Sync Loss
Bit 14
Hardware Current Limit
Motoring Current Limit
Motor OL Trip
Auto Reset
Phase Loss
Heatsink Temp
Auxiliary Input
4-20 mA Loss
Motor Therm
Bit 15
Bit 13 Bit 12 Bit 11 Bit 10 Bit 9 Bit 8 Bit 7
Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Bit 14
Unused
Encoder Loss
Load Loss
Enc Cnt Max
Enc Cnt Set
Voltage Check