Output devices, Cable termination, Output devices –37 cable termination –37 – Rockwell Automation 1336F PLUS II User Manual - Firmware 1.xxx-6.xxx User Manual

Page 47

Advertising
background image

Installation/Wiring

2–37

Output Devices

Drive Output Disconnection

Common Mode Cores

Common Mode Cores will help reduce the common mode noise at the
drive output and guard against interference with other electrical
equipment (programmable controllers, sensors, analog circuits, etc.).
In addition, reducing the PWM carrier frequency will reduce the
effects and lower the risk of common mode noise interference. Refer
to the table below.

Table 2.I
1336

PLUS

II

Common Mode Chokes

Cable Termination

Optional Cable Terminator

Voltage doubling at motor terminals, known as reflected wave phe-
nomenon, standing wave or transmission line effect, can occur when
using drives with long motor cables.

Inverter duty motors with phase-to-phase insulation ratings of 1200
volts or higher should be used to minimize effects of reflected wave
on motor insulation life.

Applications with non-inverter duty motors or any motor with excep-
tionally long leads may require an output filter or cable terminator. A
filter or terminator will help limit reflection to the motor, to levels
which are less than the motor insulation rating.

!

ATTENTION: Any disconnecting means wired to the drive
output terminals U, V and W must be capable of disabling
the drive if opened during drive operation. If opened during
drive operation, the drive will continue to produce output
voltage between U, V, W. An auxiliary contact must be used
to simultaneously disable the drive.

Catalog Number Used with . . .

Description

1321-M001

Communications Cables, Analog
Signal Cables, etc.

Open Style - Signal Level

1321-M009

All 1336

PLUS

II

Drives Rated:

480V, 0.37-3.7 kW (0.5-5 HP)

Open Style with Terminal Block, 9A

1321-M048

All 1336

PLUS

II

Drives Rated:

480V, 5.5-22 kW (7.5-30 HP)
600V, 5.5-30 kW (7.5-40 HP)

Open Style, 48A

1321-M180

All 1336

PLUS

II

Drives Rated:

480V, 30-112 kW (40-X150 HP)
600V, 37-93 kW (50-125 HP)

Open Style, 180A

1321-M670

All 1336

PLUS

II

Drives Rated:

480V, 112-448 kW (150-600 HP)
600V, 149-448 kW (200-600 HP)

Open Style, 670A

Advertising