Rockwell Automation 1336F PLUS II User Manual - Firmware 1.xxx-6.xxx User Manual
Page 23

Installation/Wiring
2–13
General Grounding
Single-Point Grounding/Panel Layout
Important: Grounding requirements will vary with the drives being used. Drives with True Earth (TE) terminals must have a zero potential bus, separate from potential
earth (PE) ground bus. Note that buses can be tied together at one point in the control cabinet or brought back separately to the building ground grid (tied within 3 meters
(10 feet)).
JOG
ESC
SEL
R (L1)
S (L2)
T (L3)
PE
U (T1)
Shield
RIO/DH+
or Analog
Common
Mode
Core*
Common
Mode Core*
Conduit/4-Wire Cable
To Computer/Position Controller
(for TE shield ground, see "
Control and Signal Wiring")
Ground per
Local Codes
Motor Frame
Motor
Terminator*
PE
V (T2)
W (T3)
PE/Gnd.
* Options that can be
installed as needed.
Nearest
Building Structure Steel
JOG
ESC
SEL
R (L1)
S (L2)
Nearest
Building Structure Steel
To Nearest Building
Structure Steel
Nearest Building
Structure Steel
1336 FORCE
1336 PLUS
T (L3)
PE
TE
Logic
PE
Logic
TE – Zero Volt Potential Bus
(Isolated from Panel)
PE Ground Bus
(Grounded to Panel)
For Programmable Controller
grounding recommendations,
refer to publication 1770-4.1