Meas. volts, Eeprom cksum – Rockwell Automation 1336F PLUS II User Manual - Firmware 1.xxx-6.xxx User Manual
Page 122

6–40
Programming
[DC Bus Memory]
This parameter displays the nominal DC bus voltage level.
This value is used to determine line loss, overvoltage, de-
cel frequency and other points. Additionally, the Bus Limit
Enable function, as well as the Line Loss Mode alarm and
recovery points are determined from this value.
Parameter Number
212
Parameter Type
Read Only
Display Units / Drive Units
1 Volt / Volts
Display
Volts
[Meas. Volts]
This parameter displays the measured output voltage
present at terminals U, V & W (T1, T2 & T3).
Parameter Number
272
Parameter Type
Read Only
Display Units / Drive Units
1 Volt / 4096 = Drive Rtd Volts
Factory Default
None
Minimum Value
0
Maximum Value
200% Rated Drive Output Voltage
[EEPROM Cksum]
The value of this parameter provides a checksum value
that indicates a change in drive programming has
occurred.
Parameter Number
172
Parameter Type
Read Only
Display Units / Drive Units
None