Using the Pre-Defined Links
The following are the pre-defined links:
The default configuration assumes that a Human Interface Module
(HIM) terminal is connected to SCANport. Speed Ref 1 is connected
to SP An In1 Value, which is assumed to be the HIM port.
Removing a Link
To remove a link, you need to:
1. From the Choose Mode prompt, use INC or DEC to select Links.
2. Press INC or DEC to select Set Links.
3. Use INC or DEC to scroll through the parameter list until you
come to the destination parameter that you want to link.
4. Press SEL.
5. Enter 0.
6. Press ENTER.
7. Press ESC when you have finished to exit the Set Links mode.
Destination
To
Source
Speed Ref 1
29
134
SP An In1 Value
Speed Ref 2
31
96
An In 1 Value
An Out 1 Value
105
81
Motor Speed
An Out 2 Value
108
90
Motor Power
To
To
To
To
SP An Output
139
81
Motor Speed
To
!
ATTENTION: Be careful when removing links. If the
source parameter has already written a value to the
destination parameter, the destination parameter retains
the value until you explicitly remove it. For some
parameters, this may produce undesirable results.