Rockwell Automation 1336E IMPACT Adjustable Frequency AC Drive User Manual V 1-4.XX User Manual
Page 40

2-22
Mounting and Wiring Your 1336 IMPACT Drive
The typical analog input connections for unidirectional operation are
shown as follows:
The typical analog input connections for bidirectional operation can
be shown as follows:
-10V DC (Power Supply)
COM (Power Supply Common)
+10V DC (Power Supply)
IN + (Analog In)
IN - (Analog In)
ADC
A
Connect to
either A or C
(only one)
B
C
D
E
Note: Connect to only one set of inputs
-- IN4+ and IN4-
-- IN3+ and IN3-
-- IN2+ and IN2-
-- IN1+ and IN1-
Reference Pot
2.5 k
Ω Minimum
To TE
(Signal Ground Terminal Block)
Shield
F
A1–A4
B–H
A
J4–3
TB10–3
B
J4–2
TB10–2
C
J4–1
TB10–1
D
J7–1
TB10–4
E
J7–2
TB10–5
F
J7–3
TB10–6
Frames
-10V DC (Power Supply)
COM (Power Supply Common)
+10V DC (Power Supply)
IN + (Analog In)
IN - (Analog In)
ADC
A
Forward
Reverse
B
C
D
E
Note: Connect to only one set of inputs
-- IN4+ and IN4-
-- IN3+ and IN3-
-- IN2+ and IN2-
-- IN1+ and IN1-
Reference Pot
2.5 k
Ω Minimum
To TE
(Signal Ground Terminal Block)
Reverse
Forward
R
Reverse
Relay
Shield
F
A1–A4
B–H
A
J4–3
TB10–3
B
J4–2
TB10–2
C
J4–1
TB10–1
D
J7–1
TB10–4
E
J7–2
TB10–5
F
J7–3
TB10–6
Frames
If you are wiring a remote pot to your system, you may want to refer
to Chapter 9, Applications, and Appendix B, Control Block
Diagrams, for additional information.