B-28 control block diagrams, File, Group – Rockwell Automation 1336E IMPACT Adjustable Frequency AC Drive User Manual V 1-4.XX User Manual
Page 366

B-28
Control Block Diagrams
Drive Fault Detection Overview, Continued
You can configure how you want some situations reported (drive
fault, warning, or ignored), while other situations are always reported
as faults. For the configurable faults, four parameters are provided:
Fault Select 1 (parameter 20), Warning Select 1 (parameter 21), Fault
Select 2 (parameter 22), and Warning Select 2 (parameter 23). For
information about these parameters, refer to Chapter 12,
Troubleshooting.
This section explains how some of the faults are caused and detected.
41
T
C
24
40
FV
>
Warn
<–20˚C
Or
>100˚C
0.5 Sec
Delay
R
F
Not Drive Stopped
Bound Check
Absolute
Overspd
Fwd Motor
Speed Limit
Code
2028
Fault Code 3025
Filtered
Speed
Feedback
Rev Motor
Speed Limit
Absolute Overspeed
100 msec
Delay
Inverter Temperature Check
Power Transistor
Heat Temperature, ˚C
Fault Code 2049
Inverter Overtemp Pending
0.5 Sec
Delay
Look–up
Table
NTC
Input
Power Transistor
Heatsink Temperature
(NTC)
10
15
Drive/Inv
Status
(13V – 18V)
200 msec
Delay
Analog Supply Tolerance
Scale
15 Volt
Analog
Supply
Fault Code 3026
Non–Configurable Faults
file:
Fault Setup
group:
Fault Config