Mounting and Wiring Information Specific to Frames B, C, D, E, F, G, and H
4-9
The terminal blocks provide the following:
The voltage clearance provides physical space between the logic earth
ground and other signals on the terminal block.
This
terminal
block:
Provides these terminal
numbers:
Which provide access to this signal:
TB10
6, 9, 12, 17, 20
Shield ground
1, 2, 3
DC power supply
± 10V DC
50 mA per voltage
4, 5, 7, 8
0 to
±10V DC Input
Input impedance = 20K Ohms
10, 11
4 – 20 mA input
Input impedance = 130 Ohms
13, 14
Pulse input for frequency reference
+5V DC — Jumper J4 Set to 1 – 2
+12V DC — Jumper J4 Set to 2 – 3
Scale Factor (Pulse PPR) must be set
10mA minimum
15, 16, 18, 19
0 to
±10V DC output
Output impedance = 100 Ohms, 10mA maximum
21, 22
4 – 20 mA DC output
Output impedance = 20 Ohms
TB11
10
Logic Earth Ground, Shield
1, 2, 3,
Programmable contacts
4, 5, 6,
Resistive rating = 115VAC/30VDC, 5.0A
7, 8, 9
Inductive rating = 115VAC/30VDC, 2.0A