This works as shown in figure 10.11 – Rockwell Automation 1336E IMPACT Adjustable Frequency AC Drive User Manual V 1-4.XX User Manual
Page 179

Using the Function Block
10-9
Figure 10.9
Speed Profiler Using the State Machine Function Block
To set up the function block for this application, you would need to
enter the values shown in Figure 10.10.
Figure 10.10
State Machine Function Block
This works as shown in Figure 10.11.
Speed
(rpm)
Time (seconds)
4000
1024
0
0
1
2
3
4
200
Func 1 Eval Sel
10
198
Function In1
199
Func 1 Mask/Val
Enter: 4000
State Machine Function Block
203
Func 2 Eval Sel
10
201
Function In2
202
Func 2 Mask/Val
Enter: 1024
212
Function Sel
In1 is true if
Motor Speed > 4000
206
Func 3 Eval Sel
0
204
Function In3
205
Func 3 Mask/Val
Enter: 0
Enter: 0 This value is not used.
In3 = 0
207
Function In4
208
Function In5
Enter: 0
Enter: 0.17 minutes (10 seconds)
213
Function
Output 1
8
And In1
Then this
If In2 is: Timer is:
output is used:
False
False
In3 — 0
False
True
In6 — Not used
True
False
In7 — Ramp Disable
True
True
In8 — Ramp Disable Stop
209
Function In6
210
Function In7
Enter: 0 This value is not used.
Enter: 00000010.00000000
211
Function In8
Enter: 00000010.00000001
In4 Off Time
= 0
In5 On Time
= 100
197
Logic Cmd
Input
81
Motor Speed
In2 is true if
Motor Speed > 1024
81
Motor Speed