Rockwell Automation 999 IMC S Class Compact Motion Controller (Cat. No. 4100-999-122) User Manual
Page 135
 
Understanding IMC-S/23x Setups
5-55
Publication 999-122 - January 1997
If the selected block has not been configured in the GML Definitions 
menu, the message
is displayed. The Flex I/O connected to the IMC-S/23x must be 
configured before it can be tested. See The Definitions Menu in the 
GML Programming Manual for IMC S Class Motion Controllers 
(999-104) for information on configuring Flex I/O modules.
When this test is run, the current state (on or off) of the first four inputs 
is continuously displayed as shown below.
Manually activate the devices connected to the displayed inputs and 
verify that the state (
ON
or
OFF
) displayed beneath each input label
changes properly. Press ENTER to test the next group of discrete inputs 
or to terminate the discrete input test.
Checking Flex I/O Discrete Outputs
Discrete outputs on Flex I/O 1794-OB16 or 1794-OA8 modules are 
tested in groups of four using the discrete output test. The IMC-S/23x 
displays
Toggle to the desired Flex I/O module to test and press ENTER. If the 
selected module is not an OB16 or OA8 discrete output module, an 
appropriate warning message is displayed and you may select another 
block. 
If the selected block has not been configured in the GML Definitions 
menu, the message
is displayed. The Flex I/O connected to the IMC-S/23x must be 
configured before it can be tested. See The Definitions Menu in the 
GML Programming Manual for IMC S Class Motion Controllers 
(999-104) for information on configuring Flex I/O modules.
Test Module
This Module is NOT CONFIGURED!
INPUT0 INPUT1 INPUT2 INPUT3
OFF OFF OFF OFF
Run Discrete Output Test? YES
Test Module 0
Test Module
This Module is NOT CONFIGURED!