Rockwell Automation 999 IMC S Class Compact Motion Controller (Cat. No. 4100-999-122) User Manual
Page 87
 
Understanding IMC-S/23x Setups
5-7
Publication 999-122 - January 1997
Next the IMC-S/23x asks
Toggle to
YES
and press ENTER if you plan to use DH-485 in your
application. To temporarily disable DH-485, toggle to
NO
and press
ENTER. To permanently disable DH-485, the hardware must be 
re-configured (see Configuring the IMC-S/23x in the Installation and 
Hookup section of this manual).
Maximum Node Address
Enter the highest address of any device on the DH-485 network for 
the maximum node address. This is the highest address which will be 
polled as devices pass the token among masters on the DH-485 network. 
The smaller the maximum node address, the faster the throughput on 
the DH-485 network, since no time is spent polling devices which do 
not exist. 
Network Node Address
Enter the desired address of the motion controller on the DH-485 
network for the network node address. The specified address must 
be less than or equal to the specified maximum node address. If not, 
the message
is displayed and you must enter a new network node address.
Baud Rate
Toggle to the baud rate of the DH-485 network to which the motion 
controller is connected. Both 19,200 and 9,600 baud are available. 
Unless necessary for some other device, always use 19,200 baud for 
fastest communication. 
Token Hold Factor
Toggle to the hold factor you want (1, 2, 3, or 4). Selecting the 
default of 4 gives the IMC-S/23x the largest time slice for sending 
and receiving.
Edit DH-485 Config? YES
DH-485? NO
Address Must be < than Max. Address!
Network Node Address?