Understanding IMC-S/23x Setups
5-71
Publication 999-122 - January 1997
Setting the Integral Gain
Once the proportional and velocity gains have been tuned or set as 
explained above, small amounts of integral gain may be added to 
improve static positioning accuracy. If you are using an analog velocity 
loop servo amplifier, set the integral gain to zero–most analog velocity 
loop servo amplifiers will not tolerate any amount of integral gain 
without producing severe oscillations. With a digital velocity loop servo 
amplifier, the velocity integrator in the amplifier must be disabled to 
use I gain in the motion controller.
If you are using a torque (current) loop servo amplifier, set the I gain 
using the formula below.
I Gain = 250 x (P Gain)
2
Alternately, increase the integral gain starting at 0 until the motor 
sustains oscillation for a few seconds or more. The optimal I gain value 
is about 50% of this value. Notice that as the I gain is increased, the 
system becomes "tighter" at standstill, but also tends to become more 
unstable or "jittery". In general, the smallest integral gain value that 
gives a reasonably tight system without excessive jittering at standstill 
is best. Too much integral gain causes severe instability!
If you are converting the integral gain from a basic (IMC-S/20x) or 
integrated (IMC-S/21x) IMC S Class motion controller, calculate the 
equivalent I gain for the IMC S Class Compact (IMC-S/23x) using the 
formula below.
Compact I gain = 1,000 x (Basic/Integrated I gain)
For example, if a basic or integrated IMC S Class had previously been 
used successfully on this axis with an I gain of 0.003, the equivalent I 
gain for the IMC S Class Compact is 3.