Configuring the Ethernet Channel for Local Communication
Publication 1747-10.4
If you do not use “Auto-Configure”, you must enter the channel 0
default parameters as follows:
•
Device Type: SLC-CH0
•
Baud Rate: 19200
•
Parity: None
•
Error Checking: CRC
•
Stop Bits: 1
•
Protocol: Full Duplex
When finished, click “OK”. “AB_DF1-1 DH485 Sta:0 COMn:
RUNNING” is added to the list of configured drivers (where n =
the number of the COM port you selected).
Minimize the RSLinx window.
4. Start RSLogix500 programming software and create a new file.
5. In the “Select Processor Type” window, choose the SLC 5/05
processor type:
•
1747-L551, 16K memory
•
1747-L552, 32K memory
•
1747-L553, 64K memory
Assign a name to the processor and click “OK”. A ladder
programming screen appears showing only an END rung.
6. Using the list on the left side of the screen, double-click on
“Controller Properties” under the “Controller” category (folder).
7. In the “Controller Properties” window, click on the “Controller
Communications” tab. In this window, select “AB_DF–1” as the
driver. Click “OK”.
8. Using the list on the left side of the screen, double-click on “I/O
Configuration” under the “Controller” category.
9. In the “I/O Configuration” window, you can identify your SLC
hardware (chassis and I/O modules) either manually or
automatically.
Note:
For automatic configuration, you need to have
your SLC hardware installed and the
programming cable (1747-CP3 or equivalent)
connected between the SLC 5/05 channel 0 and
the PC COM port.
Manually –
In the “I/O Configuration” window, select the chassis and I/O
modules that you have. Close this screen (click the close button
[x] in the upper right corner of the window).