Rockwell Automation 1747-L55x,D174710.4 SLC 500 Ethernet User Manual

Page 35

Advertising
background image

4–5

Communicating on the Ethernet Network

Publication 1747-10.4

SLC 5/05 Channel 1 (Ethernet port)

MSG Control Block with Logical ASCII Addressing

valid for PLC-5 typed read or write only

WORD

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

0

EN

ST

DN

ER

CO

EW

NR

TO

Error Code

1

Reserved (Target Node Not Used)

2

Number of Elements

3

Not Used

4

File Type (based on local source or destination address)

5

Not Used

6

Not Used

7

Reserved (Internal Messaging Bits)

WQ

8

Message Timer Preset

9

Message Timer Scaled Zero

10

Message Timer Accumulator

11

Data Length in Bytes

12

AO=1

Reserved (Internal Messaging Bits)

Reserved

13

Reserved

14

Logical ASCII Address String Length including NULL Termination Character (bytes)

15

First Byte of ASCII Address String

Second Byte of ASCII Address String

16

Third Byte of ASCII Address String

55

Eighty-First Byte of ASCII Address String

NULL Byte of Longest ASCII Address String

56

First Byte of IP Address String

Second Byte of IP Address String

57

Third Byte of IP Address String

76

Forty-First Byte of IP Address String

NULL Byte of Longest IP Address String

77

Reserved

Reserved (Ethernet Message Type); must be 0

78–92

Reserved for Future Use

The IP Address string format is up to 42 ASCII characters including a terminating NULL character. The first byte in the array is the
left-most character in the string as written. For example: If the IP Address is 423.156.78.012, the first byte is the ASCII character “4”. If
the MSG destination is an INTERCHANGE client on a host computer, the destination is specified as “client” and stored as a NULL
terminated string.