5–4
Using RS232-to-Ethernet
Channel-to-Channel Passthru
Publication 1747-10.4
SLC 5/03 Using DF1
The message ladder logic, message setup, and channel configurations
for the SLC 5/03 using DF1 are shown below.
SLC 5/03 Message Ladder Logic
SLC 5/03 Message Setup
•
Channel is set to zero for DF1 full-duplex protocol.
•
Target Node is the station address in the SLC 5/05 #1 routing
table where the IP address for SLC 5/05 #2 is stored.
•
The Message Timeout must be at least as long as the SLC 5/05
timeout for Ethernet connection. The SLC 5/05 default timeout is
23 seconds.