5–7
Using RS232-to-Ethernet
Channel-to-Channel Passthru
Publication 1747-10.4
Passthru Routing Table
The passthru routing table is located under the channel configuration
selection in RSLogix 500 Programming Software. If a Passthru
Routing Table File number was entered in the General Tab in the
Channel Configuration dialog box, click on the + in front of
“Channel Configuration” to reveal the routing table selection.
Double-click on “Routing Table” to view and modify the passthru
routing table.
Important:
The routing table must contain the IP address of SLC
5/05 #2 at station target node three, as shown in the
routing table above. Target node three was identified as
the target node in the SLC5/03 Message Setup dialog
box.