Configuring the Ethernet Channel for Local Communication

Publication 1747-10.4

C. Replace

xxyy

with the last four digits of the hardware

address. Use only valid hexadecimal digits (0-9, A-F); do
not use the hyphens that separate the numbers. (You will
find the hardware address on a label affixed to the printed
circuit board of the SLC 5/05 processor. Note: See page
1–2 for an illustration showing the location of the hardware
address.)

4. Save, close, and make a backup copy of this file.

Example
In this example, there are three SLC 5/05 processors and an HP 9000
programming terminal. The names and hardware addresses are
device specific:

Device

Name

IP Address

Hardware Address

SLC 5/05

sigma1

12.34.56.1

00–00–BC–1D–12–34

SLC 5/05

sigma2

12.34.56.2

00–00–BC–1D–56–78

SLC 5/05

sigma3

12.34.56.3

00–00–BC–1D–90–12

HP 9000
(HP-UNIX)
computer)

802.3/Ethernet (TCP/IP)

SLC-5/05
processor

sigma1

BOOTP
server

SLC-5/05
processor

sigma2

SLC-5/05
processor

sigma3

Based on this configuration, the

BOOTPTAB

file looks like:

#

Legend:

gw

––

gateways

#

ha

––

hardware

address

#

ht

––

hardware

type

#

ip

––

host

IP

address

#

sm

––

subnet

mask

#

vm

––

BOOTP vendor extensions format

#

tc

––

template host

#Default string for each type of Ethernet client

defaults5E: ht=1:vm=rfc1048

#Entries for SLC 5/05 processors:

sigma1: tc=defaults5E:ip=12.34.56.1:ha=0000BC1D1234

sigma2: tc=defaults5E:ip=12.34.56.2:ha=0000BC1D5678

sigma3: tc=defaults5E:ip=12.34.56.3:ha=0000BC1D9012

1 = 10MB Ethernet