4–12

Communicating on the Ethernet Network

Publication 1747-10.4

Using BOOTP to Configure Channel 1 for Processors on Subnets

Configure the

BOOTPTAB

file according to the subnet mask and

gateway address for each SLC 5/05 processor on the link. See the
example below and the corresponding

BOOTPTAB

file on the

next page.

Important: Because BOOTP requests are seen only on the local

subnet, each subnet needs its own BOOTP server and

BOOTPTAB

file.

Ethernet gateway
or “router”

SLC 5/05
processor

Ethernet TCP/IP network

personal computer WINDOWS
or HP 9000 or VAX computer

Hostname:

Iota2

IP address:

130.151.132.110

Subnet Mask:

255.255.255.0

Gateway
Address:

130.151.132.1

Hostname:

Iota3

IP address:

130.151.138.123

Subnet Mask:

255.255.255.0

Gateway
Address:

130.151.138.1

Hostname:

Iota1

IP address:

130.151.194.19

Subnet Mask:

255.255.255.0

Gateway Address:

130.151.194.1

130.151.194.xxx

130.151.132.xxx

130.151.138.xxx

Subnet A

Subnet B

Subnet C

BOOTP
server

BOOTP
server

BOOTP
server

130.151.132.1

130.151.138.1

130.151.194.1

SLC 5/05
processor

SLC 5/05
processor