Rockwell Automation 1747-L55x,D174710.4 SLC 500 Ethernet User Manual

Page 55

Advertising
background image

5–11

Using RS232-to-Ethernet

Channel-to-Channel Passthru

Publication 1747-10.4

Example 2: DH485-to-Ethernet and Ethernet-to-DH485

In the following diagram, the SLC 5/03 uses DH485 protocol to send
a remote message to SLC 5/05 #1. The SLC 5/05 #1 passes the
message through to SLC 5/05 #2 via Ethernet. The SLC 5/05 #2 can
also send a message to the SLC 5/03 via the SLC5/05 #1 bridge.
The SLC 5/05 #1 processor routes the message to the SLC 5/03 via
DH485.

Important:

In the SLC 5/05 #1 bridge, Status File Bit S:34/0 must
be set to 0 to enable DH485-to-Ethernet passthru. Set
Status File Bit S:34/5 to 0 to disable DF1-to-Ethernet
passthru.

SLC 5/03

Channel 1

DH485 Node 1

SLC 5/05 #1 Bridge

Channel 0

DH485 Node 2

IP Address 130.151.81.104

SLC 5/05 #2

IP Address 130.151.81.139

Ether

net

Ethernet Port

DH485

DH485

DH485

Ethernet Hub

1747-PIC

Interface

Converter

RS232 Port

Personal Computer

with

RSLinx and RSLogix 500

1747-AIC

1761-NET-AIC

1747-C11 Cable

SLC 5/03 Using DH485

The remote message ladder logic, setup, and channel configuration
are shown on page 5–12.