A - specifications, System test general specifications, Specifications – Rockwell Automation 1747-L55x,D174710.4 SLC 500 Ethernet User Manual

Page 65: Appendix

Advertising
background image

Appendix

A

Publication 1747-10.4

Specifications

The table below lists SLC 500 system test specifications.

Description

Specification

Industry Standard

Temperature

Operating: 0

°

C to +60

°

C (32

°

F to 140

°

F)

Not Applicable

Temperature

Storage: –40

°

C to +85

°

C (–40

°

F to 185

°

F)

Not Applicable

Humidity

5 to 95% without condensation

Not Applicable

ibration

Operating: 1.0G at 5 to 2000 Hz

Not Applicable

Vibration

Non-operating: 2.5Gs at 5 to 2000 Hz

Not Applicable

Operating: 30.0Gs (3 pulses, 11 ms)

Not Applicable

Shock

Operating: 10.0Gs (3 pulses, 11 ms)

Not Applicable

Non-operating: 50.0Gs (3 pulses, 11 ms)

Not Applicable

Free Fall (drop test)

Portable, 2.268 kg (5 lbs) or less at 0.762m
(30 in.) (six drops)

Not Applicable

Free Fall (drop test)

Portable, 2.268 kg (5 lbs) or more at 0.1016m
(4 in.) (three flat drops)

Not Applicable

Showering Arc: 1.5 kV

NEMA ICS 2-230/NEMA ICS 3-304

Surge Withstand Capability: 3 kV

IEEE Std. 472-1974/ANSI C37.90/90A-1974

Electromagnetic Compatibility

Fast Transient Burst (impulse): 2 kV for 1746
power supplies, 1kV for 1746 I/O and
communication lines over 10m (32.84 ft), 5 ns
rise time

Internal Rockwell Automation standard

Electrostatic Discharge (ESD): 15 kV,
100 pF/1.5k ohm model

Internal Rockwell Automation standard

Radiated Electromagnetic Susceptibility: 5W
walkie-talkie at 464.5 MHz and 153.05 MHz

Internal Rockwell Automation standard

Dielectric Withstand: 1500V ac

UL 508, CSA C22.2 No. 142

Safety

Isolation between Communication Circuits:
500V dc

Not Applicable

Safety

Isolation between Backplane and I/Os: 1500V
ac

Not Applicable

Flammability and Electrical Ignition: UL94V-0

Not Applicable

Certification

UL listed/CSA approved
Class 1, Groups A, B, C or D, Division 2
CE compliant for all applicable directives

Not Applicable

Internal Rockwell Automation standards are based on Rockwell Automation’s extensive experience in industrial controls.
It is also based partly on industry and/or military specifications.

System Test General
Specifications

Advertising