Rockwell Automation 1747-L55x,D174710.4 SLC 500 Ethernet User Manual
Page 56
Advertising
![background image](/manuals/579089/56/background.png)
5–12
Using RS232-to-Ethernet
Channel-to-Channel Passthru
Publication 1747-10.4
SLC 5/03 Ladder Logic
SLC 5/03 Message Setup
•
Channel is set to one, the DH485 default.
•
Target Node is the address in the SLC 5/05 #1 routing table
where the IP address for SLC 5/05 #2 is stored.
•
The Message Timeout must be at least as long as the SLC
5/05 timeout for Ethernet connection. The SLC 5/05 default
timeout is 23 seconds.
•
The Remote Bridge Link ID is the Link ID of Channel 1 of
the SLC 5/05 #1 bridge.
•
The Remote Bridge Address is always zero to point to the IP
address for the bridge’s (SLC 5/05 #1) Ethernet channel.
•
The Local Bridge Address is the Channel 0 DH485 node
address of the SLC 5/05 #1 bridge.