Overview of the Very High Speed Counter Module

returns in status either count or frequency in binary or BCD
format

input counts as high as 999,999

up to 500KHz in period/rate or rate measurement frequency
modes

outputs can be tied to any counter

each output has a user-selectable on-off value

outputs can be tied back to an input for cascading

automatic default configuration

each counter has a user-selectable preset and rollover value

period/rate w/periodic outputs and period/rate w/dynamic outputs
can be used for totalization

The 1771-VHSC module operates in the following modes:

counter mode

encoder X1 mode

encoder X4 mode

period/rate mode

rate measurement frequency mode

continuous/rate mode

The operation of the module in these modes is described below.

The operation of encoder and counter modes is virtually identical.
The only difference between the two modes is in the type of
feedback used.

Use the counter mode if you need the module to read incoming
pulses from a maximum of four encoders (single-ended or
differential), counters, pulse generators, mechanical limit switches,
etc. and return them to the programmable controller as a binary or
BCD number (0-999,999). In counter mode, the module accepts only
one channel feedback.

Use the encoder modes if you need the module to read incoming
quadrature pulses and return them to the programmable controller as
a binary or BCD number (0-999,999). In these modes, the module
accepts two-phase quadrature feedback and counts up or down
depending upon the condition of the phase B input for each counter.

The operation of the module in the encoder/counter modes is as
follows:

Operation in Encoder or

Counter Mode